RLC-SVD03A-EN

81

Variable Speed Fan System

Bus Overvoltage Fault

2

Motor Overload Fault

3

Low Bus Voltage Fault

4

PWM Generator Fault

5

Logic Fault

6

Stalled Motor Fault

7

Fault Descriptions

Bus Overcurrent Fault: DC Bus Current exceeds the drive rated peak
current.

Bus Overvoltage Fault: DC Bus Voltage exceeds 400 VDC on 200/230 VAC
input units or exceeds 800 VDC on 400/460 VAC input units.

Motor Overlad Fault: The drive operated in current limit (110 % of rated
current) for a period of 60 consecutive seconds. If the motor current reduces
to less than 110 % and the motor reaches commanded speed the overload
timer will begin to count down.

Low Bus Voltage Fault: DC Bus Voltage is less than 200 VDC on a 200/230
VAC input unit or is less than 400 VDC on a 400/460 VAC input unit. If the
motor is already running, this fault will not occur. Instead, the motor speed
will be reduced to a speed that the proper voltage can be applied to the
motor.

PWM Generator Fault: The drive failed to switch a PWM output properly.

Logic Fault: The Microcontroller in the drive executed an illegal instruction.

Stalled Motor Fault: Motor failed to accelerate to ½ the motor speed setpoint
in 30 seconds.

Automatic Restart: If the drive should fault, the drive will automatically
attempt one restart after a delay of 5 seconds. If the drive faults a second
time, the drive will not attempt to restart and the fault must be cleared before
the drive will run again.

Fault Clearing:

Drive Faults may be cleared by one of the following methods:

Removing and reapplying power to the controller.

Setting the speed control input duty cycle to less than 7% for 1 second.