Module Power and Miscellaneous I/O

specified, unless otherwise indicated. The first terminal in the pair is the
positive (or hot) terminal. Voltages given are nominals and may vary by ±5%.
Unregulated Voltages (unreg) or 115 VAC voltages may vary by ±15%.

Table 21

EXV Module Normal Terminal Voltages

Terminal
Designation

Description
of Circuit

Normal Terminal Voltages
for Various Conditions.

J1-4 to 3
or J1-2 to 1

IPC Communications

19.2 kbaud serial data, 5 volt signal level.
Refer to Interprocessor Communication Link (IPC).

J2-2, 1

Manufacturing
Address Use Only

+5 VDC No connection intended.

J3-9, 8

Saturated Evap.
Rfrg. Temp. CKT 1

Refer to Temperature Sensor Checkout.

J3-7, 6

Compressor Suct.
Rfrg. Temp. CKT 2

Refer to Temperature Sensor Checkout.

J3-4, 3

Saturated Evap.
Rfrg. Temp. CKT 2

Refer to Temperature Sensor Checkout.

J3-2, 1

Compressor Suct.
Rfrg. Temp. CKT2

Refer to Temperature Sensor Checkout.

J4-5

1

EXV CKT1 GND

OVDC GND.

J4-3

1

EXV CKT1 Phase 1

Between 0 and 1 VDC when the phase is not being stepped. When
the valve is being stepped, this signal is actually a 24.2±17% VDC
peak square wave with a period of 60 msec and a 1/3 duty cycle
low (On) and 2/3 duty cycle high (Off). An averaging DC voltmeter
can be used to measure this voltage. The meter will show fluctua-
tions but the average should be approximately 8 volts.

J4-2

1

EXV CKT1 Phase 2

J4-1

1

EXV CKT1 Phase 3

J5-6

1

EXV CKT2 GND

OVDC GND.

J5-4

1

EXV CKT2 Phase 1

Same a CKT 1.

J5-2

1

EXV CKT2 Phase 2

Same as above.

J5-1

1

EXV CKT2 Phase 3

Same as above.

J4-1, 2, 4,5

2

EXV CKT 1

10-12 VDC

J4-1, 2, 5, 6

2

EXV CKT 2

10-12 VDC

J6-1 or 2
to J6-4 or 5

Input Power

115 VAC, Refer to

Power Supply on page 41

.

J7-5, 4

Low Pressure
Switch, Circuit 1

Open = 12 VDC, Low Pressure Cutout
Closed = 0 VDC, Normal

J7-2, 1

Low Pressure
Switch, Circuit 2

Open = 12 VDC, Low Pressure Cutout
Closed = 0 VDC, Normal

Note: On a power up or a front panel reset, the valve will always be driven closed for approximately 1000 steps. During this time,

approximately 40 seconds, an alternating audible clicking sound can be observed on the valves

1

SEO Valve

2

SEHI Valve