In” in, Table 9, Current transformer – Trane RTWA 70-125 TON User Manual
Page 31
RLC-SVD03A-EN
31
Current Transformer
Table 9
Overload Dip Switch Setting vs. Internal Software Gain
CPRSR RATED RLA
AS A % OF CT RATING
OVERLOAD DP
SWITCH SETTING
DECIMAL
SETTING
SOFTWARE
GAIN
66
00000
00
1.500000
67
00001
01
1.483870
68
00010
02
1.467743
69
00011
03
1.451613
70
00100
04
1.435483
71
00110
06
1.403226
72
00111
07
1.387097
73
01000
08
1.370969
74
01001
09
1.354839
75
01010
10
1.338709
76
01011
11
1.322580
77
01100
12
1.306452
78
01101
13
1.290323
79
01111
15
1.258065
80
01111
15
1.258065
81
10000
16
1.241936
82
10001
17
1.225806
83
10010
18
1.209678
84
10011
19
1.193549
85
10100
20
1.177419
86
10101
21
1.161291
87
10110
22
1.145162
88
10110
22
1.145162
89
10111
23
1.129032
90
11000
24
1.112903
91
11001
25
1.096775
92
11001
25
1.096775
93
11010
26
1.080645
94
11011
27
1.064516
95
11100
28
1.048387
96
11100
28
1.048387
97
11101
29
1.032258
98
11110
30
1.016128
99
11110
30
1.016128
100
11111
31
1.000000