Module power and miscellaneous i/o – Trane RTWA 70-125 TON User Manual
Page 56
56
RLC-SVD03A-EN
Module Power and Miscellaneous I/O
Table 19
CSR Normal Terminal Voltages for Options Module 1U2
Terminal
Designation
Description
of Circuit
Normal Terminal Voltages
for Various Conditions
J1-4 to 3
or J1-2 to 1
IPC Communications
19.2 kbaud serial data, 5 volt signal level.
Refer to Interprocessor Communication Link (IPC).
J2-2, 1
Manufacturing
Address Use Only
+5 VDC No connection intended.
TB1-3
+5V Source for use with
Resistor programming of CW
setpoint
+5VDC open circuit with respect to chassis ground.
TB1-3, 5
Ext. Chilled Water Setpoint
(Resistive option)
Refer to
External Setpoint Inputs (4-20ma/2-10VDC) on page 50
.
TB1-4, 5
Ext. Chilled Water Setpoint
(Current or Voltage option)
Refer to
External Setpoint Inputs (4-20ma/2-10VDC) on page 50
.
TB1-6
+5V Source for use with
Resistor programming of CL
setpoint
+5VDC open circuit.
TB1-6, 8
Ext. Current Limit Setpoint
(Resistive option)
Refer to
External Setpoint Inputs (4-20ma/2-10VDC) on page 50
.
TB1-7, 8
Ext. Current Limit Setpoint
(Current or Voltage option)
Refer to
External Setpoint Inputs (4-20ma/2-10VDC) on page 50
.
TB1-9, 10
Unused
TB2A-1,2
or TB2B-3,4
Serial Comm.Input
Refer to Section 2, ICS Communications.
J6-1 or 2
to J6-4 or 5
Input Power
115 VAC, Refer to
.
Dip Switch
SW1-1
External Chilled Water Setpoint
Dip Switch
Off for 2-10 VDC input.
On for 4-20 mA input.
Dip Switch
SW1-2
External Current
Limit Setpoint
Dip Switch
Off for 2-10 VDC input.
On for 4-20 mA input.