Dimensions/weights, Dimensions/weights/ clearance, Warning improper unit lift – Trane GETB User Manual
Page 6

6
WSHP-SVN08B-EN
ALLOW 36" (914 mm)
AT UNIT FRONT FOR
CHASSIS REMOVAL
R
S
D
Table 1: Unit weights
Size
Shipping
Weight
with pallet (lb)
Shipping
Weight
w/o pallet (lb)
Cabinet
009
135
115
012
135
115
015
175
150
018
175
150
024
225
195
036
225
195
Chassis
009
90
80
012
95
85
015
110
100
018
115
105
024
190
180
036
200
190
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
Dimensions/Weights/
Clearance
Figure 1: Mechanical clearances
Unit Location and Clearances
Locate the unit in an indoor area. The
ambient temperature surrounding the
unit must not be less than 45°F. Do not
locate the unit in areas subject to
freezing.
Attention should be given to service
clearance and technician safety. The
unit chassis should be easily removed
from the cabinet in all applications.
There must be enough space for ser-
vice personnel to perform mainte-
nance or repair. Provide sufficient
room to make water, and electrical
connection(s). Local and national
codes should be followed in providing
electrical power connections. See Fig-
ure 1 for mechanical clearances.
!