beautypg.com

Installation – Trane GETB User Manual

Page 13

background image

WSHP-SVN08B-EN

13

1 Secure the door frame to the side

studs using the holes located in the
door frame and field provided
screws, Figure 6.

Note: If the gap between the door
frame, and the side stud is over 1/16-
inch, place a shim in between the door
frame and the stud to prevent the door
frame from bending/denting.

2 Place the air panel into the door

opening. The gasket on the back
side of the air panel should seal
around the coil perimeter, Figure 7.

3 After verifying that the air panel gas-

ket is sealed to the coil, secure the
air panel to the door frame using the
slots located on the sides of the air
panel, Figure 8.

4 Install Filter.

5 Vacuum all dust and construction

debris from unit after cutting out
supply/return openings.

Supply Air Ductwork
1 A 2" (50.8 mm) duct flange (field

provided) may be required to help
eliminate supply air from recirculat-
ing back into the return air, air-to-re-
frigerant coil prior to discharging
into the space.

2 Equipment containing a top dis-

charge, ducted design: install field
ductwork to the unit providing a wa-
ter tight flexible connector at the
unit. This helps prevent operating
sounds from transmitting through
the ductwork. Elbows with turning
vanes or splitters are recommended
to minimize air noise due to turbu-
lence and to help reduce static pres-
sure.

Chassis Installation
1 Remove three 16-inch bolts on the

chassis and discard, Figure 9.

Figure 9: Shipping bolts

2 Rotate the triangular metal plate to

cover the bolt holes in the chassis.
Secure with two sheet metal screws.

3 Remove two shipping brackets (one

on each side) attached to the chassis
slide rails and discard, Figure 10.
Note: Remove this bracket only if
the enhanced sound package design
is preferred.

Figure 10: Bracket removal for
enhanced sound package

4 Connect water coil pipe to the sys-

tem riser with a flexible steel hose
assembly.

5 Verify that the shut-off/balancing

valve in the return line/supply line
are closed.

6 Place shut-off valves in appropriate

location (see sticker on the equip-
ment for best placement recom-
mendation) to allow chassis to slide
easily in/out of unit cabinetry.

Installation

Figure 6: Door opening

Figure 7: Air panel gasket

Figure 8: Secure to door frame