Table F2: Blower External Static Pressure with Return Air Door (RAD), with filter

1

The NO "Ducted" option is for non-ducted (free return) units.

2

Units specified as "non-ducted" (free return) are factory wired to low-speed.

3

Units specified as "ducted" are factory wired to high-speed.

Table E1: Electrical Performance

Model No.

Speed

Tap

Ducted

Min

CFM

Max

CFM

External Static Pressure (in. of wg)

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0.55

0.6

0.65

0.7

GET009

High

Yes

280

482

-

451

417

378

342

303

-

-

-

-

-

-

-

-

-

GET009

Low

Yes

-

-

-

336

324

304

278

-

-

-

-

-

-

-

-

-

-

GET009

High

No

-

-

345

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET009

Low

No

-

-

280

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET012

High

Yes

380

481

-

-

-

459

436

413

389

363

-

-

-

-

-

-

-

GET012

Low

Yes

-

-

-

420

400

382

362

-

-

-

-

-

-

-

-

-

-

GET012

High

No

-

-

470

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET012

Low

No

-

-

380

-

-

-

-

-

-

-

-

-

-

-

-

-

GET015

High

Yes

475

652

-

-

-

-

-

642

621

601

574

551

525

493

457

419

679

GET015

Low

Yes

-

-

-

572

556

541

525

509

495

476

-

-

-

-

-

-

-

GET015

High

No

-

-

575

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET015

Low

No

-

-

475

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET018

High

Yes

570

800

-

-

-

-

-

-

-

774

747

722

698

668

639

607

578

GET018

Low

Yes

-

-

-

623

617

603

588

571

555

-

-

-

-

-

-

-

-

GET018

High

No

-

-

690

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET018

Low

No

-

-

524

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET024

High

Yes

760

974

-

-

-

-

927

907

880

858

830

799

777

743

-

-

-

GET024

Low

Yes

-

-

-

831

806

789

767

746

726

-

-

-

-

-

-

-

-

GET024

High

No

-

-

940

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET024

Low

No

-

-

760

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET036

High

Yes

1135 1344

-

-

-

-

-

-

-

-

-

-

1250 1219 1188 1161 1125

GET036

Low

Yes

-

-

-

1177 1169 1159 1144 1136 1119 1102 1084 1061

-

-

-

-

-

GET036

High

No

-

-

1280

-

-

-

-

-

-

-

-

-

-

-

-

-

-

GET036

Low

No

-

-

1140

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Model No.

Oversized Blower

Volts

Total

FLA

Comp.

RLA

Comp.

LRA

Blower

Motor

FLA

Blower

Motor

HP

Minimum

Circuit

Ampacity

Overcurrent

Protective

Device

GET009

No

208/60/1

4.0

3.4

22.2

0.6

1/10

4.9

15

GET009

No

220-240/50/1

3.6

3.1

18.8

0.5

1/10

4.4

15

GET009

No

230/60/1

4.0

3.4

22.2

0.6

1/10

4.9

15

GET009

No

265/60/1

3.6

3.1

18.8

0.5

1/10

4.4

15

GET012

No

208/60/1

5.7

5.0

27.9

0.7

1/8

6.9

15

GET012

No

220-240/50/1

4.9

4.3

22.2

0.6

1/8

6.0

15

GET012

No

230/60/1

5.7

5.0

27.9

0.7

1/8

6.9

15

GET012

No

265/60/1

4.9

4.3

22.2

0.6

1/8

6.0

15

GET015

No

208/60/1

6.1

5.4

29.0

0.7

1/8

7.5

15

GET015

No

220-240/50/1

5.4

4.8

27.0

0.6

1/8

6.6

15

GET015

No

230/60/1

6.1

5.4

29.0

0.7

1/8

7.5

15

GET015

No

265/60/1

5.4

4.8

27.0

0.6

1/8

6.6

15

GET018

No

208/60/1

9.3

7.6

45.0

1.7

1/5

11.2

15

GET018

No

220-240/50/1

7.4

6.3

32.0

1.1

1/5

9.0

15

GET018

No

230/60/1

9.3

7.6

45.0

1.7

1/5

11.2

15

GET018

No

265/60/1

7.4

6.3

32.0

1.1

1/5

9.0

15

GET024

No

208/60/1

13.1

10.9

56.0

2.2

1/5

15.8

25

GET024

No

220-240/50/1

11.7

9.9

55.0

1.8

1/5

14.2

20

GET024

No

230/60/1

13.1

10.9

56.0

2.2

1/5

15.8

25

GET024

No

265/60/1

11.7

9.9

55.0

1.8

1/5

14.2

20

GET036

No

208/60/1

19.3

16.0

82.0

3.3

1/2

23.3

35

GET036

No

220-240/50/1

16.4

13.6

64.0

2.8

1/2

19.8

30

GET036

No

230/60/1

19.3

16.0

82.0

3.3

1/2

23.3

35

GET036

No

265/60/1

16.4

13.6

64.0

2.8

1/2

19.8

30