Command mode, Break/make auto restart, Commercial (power) hold time – Toshiba W7 User Manual
Page 67: Brake fault internal timer

W7 ASD Installation and Operation Manual
61
Brake Fault Internal Timer
Program
⇒
Protection Settings
⇒
Brake Fault Internal Timer
After a brake failure has occurred, the user-set Brake Fault Time clock setting
will begin to count down. Once this time has elapsed, a signal will be provided
to indicate that the brake has failed.
This signal may be used to halt a related system or to notify the user.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Break/Make Auto Restart
Program
⇒
Protection Settings
⇒
Break/Make (Auto Retry)
Enables/Disables the ability of the drive to start into a spinning motor when the
ST-to-CC connection momentarily opens and is then closed (Break/Make ST)
or after a power interruption (momentary power failure).
Settings:
Off
Power Failure
Make/Break ST
Both
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Command Mode
Program
⇒
Utilities
⇒
Command and Frequency Settings
⇒
Command
Mode Select
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc.
Settings:
(Use) (Control Terminal Strip) Terminal Block
(Use) LED Keypad
(Use) Common Serial (TTL)
(Use) RS232/RS485
(Use) Communication Card
Parameter Type — Selection List
Factory Default — Terminal Block
Changeable During Run — No
Commercial (Power) Hold Time
Program
⇒
Special Control
⇒
Commercial Hold Time
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.
Parameter Type — Selection List
Factory Default — 2.00
Changeable During Run — No
Minimum — 0.10
Maximum — 10.00
Units — Seconds