Pg speed reference setpoint #1, Pg speed reference setpoint #2, Pg speed frequency setpoint #2 – Toshiba W7 User Manual
Page 104

98
W7 ASD Installation and Operation Manual
Encoder
PG Speed Frequency Setpoint #2
Program
⇒
Frequency Settings
⇒
Speed Reference Setpoints
⇒
PG
⇒
PG Speed Frequency Setpoint #2
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
PG Speed Frequency Setpoint #2
is associated with the
PG Speed Reference Setpoint #2
See
PG Speed Frequency Setpoint #1
for further information on this setting.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
PG Speed Reference Setpoint #1
Program
⇒
Frequency Settings
⇒
Speed Reference Setpoints
⇒
PG
⇒
PG Speed Reference Setpoint #1
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents
(direction/speed) and is entered as a percentage of the
full ± range.
The range of values for this parameter is -100 to +100% of the PG input pulse
count range.
See
PG Speed Frequency Setpoint #1
for further information on this setting.
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
PG Speed Reference Setpoint #2
Program
⇒
Frequency Settings
⇒
Speed Reference Setpoints
⇒
PG
⇒
PG Speed Reference Setpoint #2
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
This parameter sets the PG input pulse count that represents
(direction/speed) and is entered as a percentage of the
full ± range.
The range of values for this parameter is -100 to +100% of the PG input pulse
count range.
See
PG Speed Frequency Setpoint #1
for further information on this setting.
Parameter Type — Numerical
Factory Default — +100.00
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
PID Feedback
Program
⇒
System Information and Setup
⇒
PID Setup
⇒
PID
Feedback Value
This parameter is read-only and is provided as a quick reference for the user
during PID setup.