beautypg.com

Class-d operation, Traditional class-d modulation scheme, Tpa3008d2 modulation scheme – Texas Instruments TPA3008D2 User Manual

Page 13

background image

www.ti.com

CLASS-D OPERATION

Traditional Class-D Modulation Scheme

0 V

−12 V

+12 V

Current

OUTP

Differential Voltage

Across Load

OUTN

TPA3008D2 Modulation Scheme

TPA3008D2

SLOS435A – MAY 2004 – REVISED JULY 2004

APPLICATION INFORMATION (continued)

This section focuses on the class-D operation of the TPA3008D2.

The traditional class-D modulation scheme, which is used in the TPA032D0x family, has a differential output
where each output is 180 degrees out of phase and changes from ground to the supply voltage, V

CC

. Therefore,

the differential prefiltered output varies between positive and negative V

CC

, where filtered 50% duty cycle yields

0 V across the load. The traditional class-D modulation scheme with voltage and current waveforms is shown in
Figure 17. Note that even at an average of 0 V across the load (50% duty cycle), the current to the load is high,
causing high loss and thus causing a high supply current.

Figure 17. Traditional Class-D Modulation Scheme's Output Voltage and Current Waveforms Into an

Inductive Load With No Input

The TPA3008D2 uses a modulation scheme that still has each output switching from 0 to the supply voltage.
However, OUTP and OUTN are now in phase with each other with no input. The duty cycle of OUTP is greater
than 50% and OUTN is less than 50% for positive output voltages. The duty cycle of OUTP is less than 50% and
OUTN is greater than 50% for negative output voltages. The voltage across the load sits at 0 V throughout most
of the switching period, greatly reducing the switching current, which reduces any I

2

R losses in the load.

13