APS 1012
Weight:
26.4 lbs.
INVERTER
Continuous power (@ 20° C):
1000 W
Surge power (5 seconds):
2000 W
Efficiency (Full Load):
88%
Minimum DC Fuse Rating:
225A
DC Input Current @ Nominal V DC
Full Load
95 A
No Load
2.2 A*
Nominal Input Volts:
12 VDC
DC Input Voltage Range:
10-15 VDC
Nominal Output Volts:
120 VAC ±5%
Nominal Output Frequency:
60 Hz ±.3%
BATTERY CHARGER
Charging Capacity DC:
10 A**
Maximum Cable Length
2 ft.
Acceptance Volts VDC:
Selectable 14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel):
13.3 V (13.6 V)
Input Voltage AC:
120 V
Input Current AC:
1.4 A**
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 75**,85, 95, or 105 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 135** or 145 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
12 A
Input Frequency:
60 Hz ±10%
Maximum Output AC (Continuous):
8.3 A
Automatic Transfer Time:
4-6 ms
* Load sense can reduce this to 1/30 of the listed current. **Factory default setting.
Specifications
(Corded Models)
200110086 120V APS MV-cabinetEn-Sp 93-2006.qxd 1/4/02 10:38 AM Page 16