beautypg.com

Electrical and pneumatic connections, Electrical connections, Remote contact closures zero/span inputs – Teledyne 300M User Manual

Page 19: Status outputs (optional), Igure, 3: r, Anel, Lectrical, Neumatic, Onnections

background image

Teledyne API Model 300M CO Analyzer Instruction Manual, 04033, Rev. A

1.6 Electrical and Pneumatic Connections

1.6.1 Electrical Connections

Output #1 Carbon Monoxide concentration - Chart Recorder (REC)

Output #2 Carbon Monoxide concentration - Data Acquisition System (DAS)

Output #3 Test function analog output

Input #4 Zero valve request

Input #5 Span valve request

Input #6 Not Used

There are 2 six-pin connector strips on the rear panel shown in Figure 1-3. The pins are divided
into 3-plus/minus pairs and have the functions shown above.

Outputs 1 and 2 have identical signals and electrical characteristics. Output 3 is the same as 1
and 2 electrically, but has analog TEST function signals routed to it. See Diagnostics in Section
5 for details.

1.6.2 Remote Contact Closures Zero/Span Inputs

Remote contact closures can be used to remotely energize the zero/span valves to do a zero or
span check. The external contact closure should be capable of switching 12 VDC at 50 ma.

Refer to Figure 1-3 for connection location. See Sections 1.8.2 and 3.6 for further details.

NOTE

Zero or span checks can be performed in any order.

1.6.3 Status Outputs (Optional)

Status outputs report analyzer conditions via contact closures located on the optional DB-50
connector on the rear panel. The contacts are NPN transistors which can sink 50 mA of DC
current. The pin assignments are listed in Table 1-1.

1-11