Quincy Compressor 50093-103 User Manual
Page 68
![background image](/manuals/207362/68/background.png)
62
UNIT OPERATING WITH HIGH DISCHARGE TEMPERATURES
PROBABLE CAUSE
CORRECTION
Clogged fluid cooler
Check fluid cooler for varnishing and rust deposits. If this
condition exists, clean cooler thoroughly in accordance with
recommended procedures of the heat exchanger
manufacturer.
Excessive ambient temperatures
Maximum ambient for proper operation is 110°F.
Incorrect fan rotation
Correct rotation with the fan pushing the air up through the
coolers.
Improper fluid
Use recommended fluids only - see fluids section.
Clogged air filter
Clean and replace as necessary.
Faulty thermal valve
Repair or replace as necessary.
Faulty gauges
Check and replace.
Airend failure
Contact a Quincy authorized distributor.
EXCESSIVE FLUID CONSUMPTION
PROBABLE CAUSE
CORRECTION
Too high fluid level in the receiver
Bring fluid level down to the recommended level by
draining the receiver. Use the fluid level gauge as a guide.
Plugged scavenger line
Clean scavenger line orifice and tube.
High fluid injection temperature
Correct the situation in accordance with the instructions in
"High Discharge Air Temperature and/or High Fluid
Temperature" section of this guide.
Too high inlet pressure
Operate continuously at 10" HgV and above.
Faulty or damaged separator
Change air/fluid separator.
Leak in fluid lines
Check for leaks and repair.
Seal failure, leaks
Replace seat assembly.
Incorrect fluid
Use recommended fluids only - see fluids section.
Rapid cycling
Consult factory.