Omega WI8XX-U User Manual
Page 78
72
GENERAL
Connection:
Screw terminals
Line Voltage/Power:
90 to 240 Vac +/-10%, 50 to 400 Hz*;
110 to 375 Vdc, equivalent voltage; 5 W
* No CE compliance above 60 Hz
Low Voltage/Power Option:
20 to 36 Vdc or 24 Vac** +/-10%; 4 W
External power source must meet Safety Agency
Approvals.
** Units can be powered safely with 24 Vac power
but, no Certification for CE are claimed.
External Fuse Required:
Time-Lag, IEC 127-3 recognized:
100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Time-Delay, UL 248-14 listed:
100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions:
0 to 50°C (32 to 122°F), 90% RH non-condensing
Protection:
NEMA-1/Type 1 front bezel
Dimensions:
48H x 96W x 127mm D (1.89 x 3.78 x 5")
Panel Cutout:
45H x 92mm W (1.772 x 3.622")
Weight:
353 g (0.78 lb)
Software:
The software packages available for the
Temperature Wireless System products are
iConnect (configuration software for the Ethernet
interface), iLog (Excel-based software for
automatic data logging), and Mail Notifier (email
alarm notification software).
INTERFACE SPECIFICATIONS
Ethernet:
Standards Compliance IEEE 802.3 10Base-T
(RJ45)
Supported Protocols:
TCP, UDP, ARP, ICMP, DHCP, DNS, HTTP, and
Telnet
LED Indicators:
Network Activity, Network Link, Diagnostics,
Receive & Power
Management:
Device configuration and monitoring through
embedded Web Server
Embedded Web Server:
Serves WEB pages (Java™ Applets) containing
real-time data and live updated charts within
definable time intervals.
WIRELESS COMMUNICATION
Standard:
DSSS; IEEE 802.15.4
Frequency
2.4 GHz (2410 MHz), 12 Channels
Network Topology:
Star Topology