beautypg.com

Raypak P-R185B To P-R405B User Manual

Page 35

background image

PILOT REMOVAL AND CLEANING
1. Disconnect pilot tubing, and wires from gas valve.
2. Remove pilot assembly from burner tray.
3. Remove pilot from bracket.
4. Remove pilot orifice and air opening (Honeywell MV

unit only), and clean with wire or small brush.

CAUTION! Do not enlarge hole in pilot orifice.

5. Reverse above procedure to reinstall.

HONEYWELL PILOT

ROBERTSHAW PILOT

Pilot

Pilot

Air
Opening

Orifice

Orifice

Fig. # 8045.1

Fig. # 8102.0

HEAT EXCHANGER REMOVAL
1. Shut water, gas and electricity off, close valves and

relieve pressure, remove relief valve. Remove side
inspection panels.

2. Remove top holding screws.
3. Remove draft diverter, lift and remove top and flue

collector. Remove inspection panels.

4. Disconnect wires from high limits and pressure

switch. Remove temperature sensor.

5. Disconnect flange nuts on inlet-outlet header, loosen

union(s) at gas pipe and slide boiler away from piping.

6. Lift heat exchanger straight up using caution not to

damage refractory.

7. Reverse above procedure to reinstall. Make sure the

insulation strips are properly replaced on top of the
refractory retainer.

35

BURNER DRAWER REMOVAL
1. Shut off main electrical power switch to heater.
2. Shut off gas upstream of heater.
3. Remove front door.
4. Disconnect gas line from gas valve.
5. Remove (2) screws that mount burner tray to unit,

and (2) screws that secure gas valve to jacket.

6. Disconnect wires that terminate at gas valve.
7. Slide out burner tray.
8. Reverse above procedure to reinstall.

GAS VALVE REMOVAL
1. Shut off gas supply to the heater. Remove gas piping

to gas valve inlet.

2. Disconnect wires, pilot tubing and bleed line, if

required.

3. Turn vertical gas pipe from manifold slightly and

unscrew gas valve.

4. Reverse above procedure to reinstall.

MAIN BURNER AND ORIFICE REMOVAL
1. Remove burner drawer. See burner drawer removal

procedure.

2. Remove screws and burner hold down bracket.

NOTE: If the heat exchanger is sooted badly, the
burner hold down bracket and spacer can become
distorted from direct flame impingement and this usually
necessitates replacement of these parts.

3. Lift burners from slotted spacers and slide from

orifices. Clean with a wire brush.

4. Orifices usually do not need to be replaced. To clean,

run either copper wire or wood toothpick through
orifice. Do not enlarge hole. To remove orifice, use
a socket wrench and remove from manifold. DO NOT
overtighten when reinstalling.

Burners

Burner Hold Down Bracket

Fig. # 9479

This manual is related to the following products: