beautypg.com

Raypak P-R185B To P-R405B User Manual

Page 18

background image

Fig. # 8149

NOTE: Do not use Teflon tape on gas line pipe thread.
A flexible sealant is recommended.

A minimum of 7" W.C. and a maximum of 14" W.C.
upstream pressure under load, and no load conditions
must be provided for natural gas or a minimum of 12"
W.C. and a maximum of 14" for propane gas.

GAS PRESSURE REGULATOR
The gas pressure regulator is preset at 4" W. C. for natural
gas, and 11" W. C. for propane gas. The pressure at the
gas valve, taken with a manometer, should be about 3.7"
W. C. natural gas (3.9" W.C. for Low NOx) and 10.5" W.
C. propane gas. If an adjustment is needed, remove seal
and turn adjustment screw clockwise to increase
pressure or counter-clockwise

_____

to decrease pres-

sure.

18

Gas

Pressure

Adjustment

GAS PRESSURE ADJUSTMENT LOCATIONS

MILLIVOLT GAS VALVES

ELECTRONIC IGNITION GAS VALVES

Robertshaw 7000
Models 185 thru 405

Gas

Pressure

Adjustment

Honeywell VR8304
Models 185 thru 405

Robertshaw 7200

Model 185

ELECTRONIC IGNITION GAS VALVES-CONTINUED

Robertshaw 7000 BDER

Model 265-335

Robertshaw 7000 DERHC

Model 405

Gas

Pressure

Adjustment

Gas

Pressure

Adjustment

Fig # 9263

Fig # 9264

Fig # 9328

Fig # 9327

Fig # 9329

Fig. # 9365

ATMOSPHERIC

LOW NOx

PIPE SIZING FOR GAS CONNECTIONS

Low NOx units are not available in propane.