Installation, Figure 22 – Rinnai 37AHB SERIES User Manual

Page 22

background image

22

Rinnai Corporation Hydronic Furnace (37AHB) Manual

Installation

Figure 22:

Circulating Pump 115V Troubleshooting - Flow Sensor (FS) Configuration

FINISH

YES

NO

CHECK

FOR LOOSE OR BROKEN

WIRES

CHECK

VOLTS ACROSS 'PUMP'

CONNECTIONS ON PCB

VAC = 115V +/-

NO

YES

PROBLEM(S) WITH 24V TO PCB

- GO TO 24V

TROUBLESHOOTING CHART

PUMP AMP

DRAW NORMAL

NO

CHECK CAPACITOR;

IF

DEFECTIVE REPLACE

COMPONENT

AND RE-CHECK

AMP DRAW

YES

RETURN TO START

NO

PUMP AMP

DRAW NORMAL

CHECK PUMP

MOTOR;

IF

DEFECTIVE

REPLACE

COMPONENT

AND RE-CHECK

AMP DRAW

NO

CONNECT PUMP DIRECTLY TO

115 VAC POWER SUPPLY

PUMP MOTOR

ENERGIZED

(1) RECTIFY

WIRING PROBLEM(S)

(2) CHECK MOTOR AND

CAPACITOR;

IF DEFECTIVE,

REPLACE

FAULTY COMPONENT(S)

RETURN TO START

NO

YES

YES

YES

CONTACT

TECH.

SUPPORT

RECONNECT WIRES

AND

CONFIRM THAT WIRING IS AS

PER WIRING DIAGRAMS

SYSTEM

WORKING

SYSTEM

WORKING

ADJUST THERMOSTAT

SET

TEMPERATURE HIGHER THAN

ROOM TEMPERATURE

PUMP

ENERGIZED

YES

NO

CHECK CAPACITOR;

IF

DEFECTIVE, REPLACE

COMPONENT

AND RE-CHECK

AMP DRAW

PUMP AMP

DRAW NORMAL

YES

NO

REPLACE

PUMP MOTOR AND

RETURN TO START

WITH DOOR SWITCH CLOSED

(SET SYSTEM IN HEATING MODE

-CALL FOR HEAT)

START

IS 'LED' ON

RAPID 'LED' FLASH

GO TO

RFH START-UP &

'LED' TROUBLESHOOTING

STEADY 'LED' FLASH

YES

YES

NO

PUMP

ENERGIZED

YES

NO

PUMP AMP

DRAW NORMAL

YES

NO