Installation, Caution – Rinnai 37AHB SERIES User Manual
Page 19

Rinnai Corporation Hydronic Furnace (37AHB) Manual
19
START-UP PROCEDURE (HEATING ONLY): 
The following conditions must be met prior to unit start
-up. 
Debris from soldering and/or other installation 
activities can cause equipment failure. Ensure that all 
associated lines and appurtenances are free of debris. 
Check to ensure that unit is secure.
Check that blower wheel rotates freely within the scroll 
housing.
Check all wiring to ensure that connections are tight.
Check all ductwork and pipe connections to ensure 
proper seal.
Check to ensure that all packaging wraps are removed 
from equipment.
Ensure that front access doors are properly installed.
Check to ensure proper connections to the appropriate 
blower speed tap (Heat /Cool – High and Low). Refer 
to Air Delivery and Capacity Charts and/or the 
appropriate wiring diagram in this manual.
Perform all safety and start-up checks for Tankless 
Water Heater as per manufacturer’s instructions. 
Having verified all preceding checks, the Furnace’s 
Start-Up Procedure is as follows: 
STEP 1:
Purge and fill system; follow appropriate
purging procedure as laid out in this manual in section 
titled “Purging and Priming the System”. 
STEP 2:
Turn on power supply to Furnace. Caution:
blower and/or circulator may start to operate if 
thermostat is on and a call is present. 
STEP 3:
Turn thermostat on and switch system to the
heating mode. The thermostat shall be set higher than 
the actual room temperature; this will cause the 
circulator to energize and initiate the heating cycle. (If 
the pump does not start, or the Furnace is not 
producing heat, refer to the Troubleshooting Section in 
this manual). 
STEP 4:
Program room thermostat as desired by
homeowner.
START-UP PROCEDURE (COOLING SYSTEM)
Refer to field supplied evaporator coil and outdoor unit 
manufacturer’s Installation Instructions for system 
hook-up, start-up instructions and refrigerant charging 
method details. 
TROUBLESHOOTING BLOWER AND/OR PUMP 
MOTOR AND CONTROLS 
If blower and/or pump motor does not run:
Turn off power and check the following:
1. Check that door switch is in the CLOSED position.
2. Check 3 amp fuse on Printed Circuit Board (PCB).
3. Check for 24 VAC between COM and 24 VAC on
PCB. If no voltage is present, check transformer.
4. Check all connections for kinks which could cause
loose connections. Ensure connections are secure.
5. Verify that approximately 120 VAC is present
across L1 and L2 (refer to wiring diagrams).
If system still fails to start, refer to Figures 20 through 
23 for additional help. 
Installation
High voltage is at all times present at motor. 
Disconnect power to the Hydronic Furnace before 
removing or replacing or servicing motor. Wait at 
least 5 min after disconnecting power before opening 
motor. Failure to follow this CAUTION could result in 
minor personal injury or product and property 
damage. 
CAUTION
TABLE 2.1: BLOWER MOTOR TROUBLESHOOTING
SYMPTOM
POSSIBLE 
CAUSES 
CORRECTIVE ACTION
Blown fuse
Turn off motor. Replace 
fuse 
Incorrect 
voltage 
Verify motor voltage 
matches system voltage 
Improper 
connections 
Turn off motor. Verify 
connections 
Blower wheel 
obstruction 
Verify blower wheel is not in 
contact with the blower 
housing. Readjust blower 
wheel position on motor 
shaft. 
Motor does 
not come up 
to full speed 
Not applied 
properly 
Check speed taps as per 
wiring diagram. 
Motor stalls 
during 
operation 
Overload 
motor 
Check for duct blockage 
and/or verify that ducting 
system is not restrictive. 
Motor vibrates 
or is 
excessively 
noisy 
Loose or 
defective fan 
Turn off motor. Tighten fan 
set screw or replace fan. 
Motor fails to 
start 
