Roberts Gorden UltraVac NEMA 4 User Manual
Page 34

ROBERTS GORDON
®
ULTRAVAC™ C
ONTROLLER
I
NSTALLATION
M
ANUAL
28
the password must be entered in order to access the
parameters again.
6.2 Altering VFD Parameters
Using the procedure described in Section 6.1.1
through Section 6.1.5
, alter the following parameters:
Parameter
Number
Parameter
Name
Factory
Default
New
Setting
P16
Units Ending
02
01
P44
Password
225
Any #
000-999
P03
Start Method
01
05