beautypg.com

Roberts Gorden UltraVac NEMA 4 User Manual

Page 18

background image

ROBERTS GORDON

®

ULTRAVAC™ C

ONTROLLER

I

NSTALLATION

M

ANUAL

12

3.3 Cable Requirements:

3.3.1 Line Power Supply:

As per individual building specification for class of
cable to be used. Use copper conductors only. To
size the cable, use the amperages of the burners
given on Page 13, Section 3.4.1, for each individual
zone.

3.3.2 Control Wiring

All control wiring (sensor, VFD control (0 - 10 Vdc),
pressure switch and RS-485 communication wiring)
may be plenum or non-plenum rated depending on
installation requirements, consult the National Elec-
tric Code

®

(NEC). Regardless of the code or its inter-

pretation, the local Fire Marshall makes the final
decision, contact the local Fire Marshall if you have
questions.

Do not run control (low voltage) wiring together
with power (line voltage) wiring in the same
conduit. Electrical signal interference or induced
current could occur and cause communication
problems.

VFD (0-10 V) control wiring and all RS-485 com-
munication wiring must be shielded.
Shielded wire
provides noise and interference isolation and
reduces the possibility of communication problems.
Pressure switch wiring is not required to be
shielded.
If electrical interference from machinery or
other sources cannot be avoided, shielded wire must
be used. All control cable specification diagrams
shown will refer to shielded cable.

3.3.3 Indoor Sensor Cable:

Shielded cable (four twisted pairs of stranded 24
AWG min. wire) is required for use with indoor
sensors. See Page 12, Figure 5 for an illustration of
the shielded cable specification to be used. See
Page 12, Section 3.3.2

to see if unshielded cable

may be used.

Unshielded Cable: AMP #57248, #219538, #219513;
Belden # 1585A, #1583A;
General Cable #C6015 or equivalent.
Shielded Cable:
Madison Cable #08CFJ10001, #08CFJ00004;
Belden #9681;
General Cable #2131673, #C1676 or equivalent.

FIGURE 5: Indoor Sensor Cable Detail

3.3.4 Outdoor Air Sensor VFD (0-10 V) signal,
Pressure Switch Cable and PC RS-485 converter
wiring:

Shielded cable (one twisted pair of 22 AWG min.
wire) is required for the outdoor air sensor, VFD
signal wiring, pressure switch wiring and RS-485 con-
verter wiring between controller #1 and PC
(RS-485 converter wiring to PC is only used if
controller is using an RS-485 Converter
Communication Package). See Page 12, Figure 6 for
an illustration of the cable specification to be used.
Shielded Cable: Belden #8451, #1503A, #8760;
General Cable #C2514 or equivalent.

FIGURE 6: Outdoor Sensor, VFD (0-10 V) Signal,
RS-485 Communications Cable and
Pressure Switch Cable Detail

3.3.5 RS-485 Communication Wire Between
Controllers:

Shielded cable (one twisted triad or two twisted pairs
of 22 AWG min. wire) is required for RS-485 commu-
nications between controllers. See Page 12, Figure 6
for an illustration of the shielded cable specification
to be used. Shielded Cable: Belden #1902, #8770
General Cable #C1670 or equivalent.

Shield Wire

Foil

Shield

Insulation

24 AWG

Minimum

Insulation

Foil
Shield

22 AWG Minimum

conductor

22 AWG Minimum

conductor

Uninsulated
Shield Wire