beautypg.com

Flue requirements - positioning – Rinnai 26i User Manual

Page 9

background image

9

Dimension Terminal

Position

Distance

A

Directly below an opening, air brick, opening windows, etc.

300mm

B

Above an opening, air brick , opening window, etc.

300mm

C

Horizontally to an opening, air brick , opening window, etc.

300mm

D

Below gutters, soil pipes or drain pipes.

75mm

E Below

eaves.

200mm

F

Below balconies or car port roof.

200mm

G

From a vertical drain pipe or soil pipe.

150mm

H

From an internal or external corner.

200mm

I

Above ground, roof or balcony level.

300mm

J

From a surface facing the terminal.

600mm

K

From a terminal facing a terminal

1200mm

L

From an opening in a car port. ( e.g. door, window) into a dwell-
ing 1200mm

M

Vertically from a terminal on the same wall.

1500mm

N

Horizontally from a terminal on the same wall.

300mm

O

From the wall on which the terminal is mounted

N/A

P

From a vertical structure on the roof.

N/A

Q

Above an intersection with roof.

N/A

FLUE REQUIREMENTS - POSITIONING

This manual is related to the following products: