Warning – Roberts Gorden EP 200 Series User Manual

Page 18

background image

EP-200 S

ERIES

P

UMP

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

12

SECTION 6: MOTOR WIRING

All wiring must comply with current wiring regulations
and any local regulations which may apply. Always
switch off the supply and disconnect before servicing.

6.1 Prior to Operation

Prior to operation of the pump in the heating system,
operation and proper rotation of the impeller must be
verified.

IMPORTANT: Improper rotation of the impeller will
not produce the vacuum required for proper system
operation.

The EP-201 motor must be wired for clockwise or
counterclockwise rotation as shown on Page 12, Fig-
ure 11
.

The EP-201 motor is wired for 1 Ø, 120 V, 60 Hz
operation. The EP-201 motor can be rewired for 230 V
operation by changing the motor connections as
indicated by the diagram on the motor connection box
cover.

Wire the pressure switch per the CORAYVAC

®

(P/N

127102NA), VANTAGE

®

EV

(P/N 151100NA) or appro-

piate controller installation manual.

FIGURE 11: EP-201 Motor Wiring

The EP-203 motor can be wired for 3 Ø, 208 V - 230 V, 60 Hz or 3 Ø, 460 V, 60 Hz operation.
The EP-203 motor rotation direction can be changed by interchanging any two leads.
Wire the pressure switch per the CORAYVAC

®

(P/N 127102NA), VANTAGE

®

EV

(P/N 151100NA) or appropiate

controller installation manual.

FIGURE 12: EP-203 Motor Wiring

WARNING

Electrical Shock Hazard

Disconnect electrical power and gas supply before

servicing.
This appliance must be connected

to a properly grounded electrical source.
Failure to follow these instructions can result in

death or electrical shock.

Ground

Screw

Oran

ge

Brown/White

Yello

w/Black

Black

Yellow

White

Bro

wn

Re

d

115V Power Supply

(Control Panel or Relay)

Motor Junction Box

Brown/W

hite

Line

Motor

Interlock

(Not Used)

Neutral

EP-201 Motor

To reverse rotation,
interchange black
and red leads.