beautypg.com

Raypak 336A User Manual

Page 25

background image

25

HEAT EXCHANGER REVERSAL PROCEDURE - STANDARD MODELS

1.

Remove right and left side access panels
(Figure 1).

2.

Disconnect wires at high limit, AGS (automatic gas
shut-off), and pressure switch on the in/out
header (Figure 2).

3.

Digital Models:

Remove the thermostat tempera-

ture sensor by loosening the compression fitting
nut (Figure 3). Re-route the sensor to the left side
of the heater.

4.

Millivolt Models:

Remove the temperature sen-

sor bulb and retainer clip from the sensor well
(Figure 4). Re-route the sensor bulb to the left side
of the heater.

5.

Remove (12) bolts holding the inlet/outlet and
return headers to the tube sheets. Clean off tube
sheet area where the gasket seats. Also clean off
the header and the gasket. Apply a non-petrole-
um-based lubricant to the gasket such as
AquaLube. Re-attach the headers to the opposite
sides, making sure they are installed in an upright
position (Figure 5). Do not over tighten. Torque
should not exceed 7 ft/lb.

6.

Reconnect high limit, AGS, and pressure switch
wires.

7.

Digital Models:

Insert the tempera-ture sensor in

the compression fitting and tighten 1/2 turn past
hand-tight.

8.

Millivolt Models:

Insert sensor bulb and retainer

clip into sensor well.

9.

Allow for water flow through the heater and check
for leaks.

10. Re-attach access panels to the opposite sides.

For ASME Models call your factory representative.

Fig. #1

Fig. #2

Fig. #3

Fig. #5

Fig. #4

This manual is related to the following products: