Regency P42-3 Zero Clearance Direct Vent Gas Fireplace

14

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

REGENCY DIRECT VENT SYSTEM (FLEX)

- Propane & Natural Gas

The diagram below shows examples of horizontal termination arrangements using two 90

o

elbows.

All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter

Regency Flex Vent
4" inner diameter
6-7/8" outer diameter

Maintain a 1-1/4" clearance to
combustibles for rigid pipe systems
and 1-1/2" for Regency Flex Vent.

Horizontal vent must be supported every
3 feet

Firestops are required at each floor
level and whenever passing through a
wall.

A vent guard may be required, check local codes.

If length "B" is increased, length "A" must be decreased by a corresponding amount.

Note: Regency Direct Vent System (Flex) is

only approved for horizontal termina-
tions.

Note:

1)

A maximum of two 90

o

elbows are permitted (two 45

o

elbows equal one 90

o

elbow).

2)

A minimum of 6 ft.(1.8m) vertical from base of unit is required if two 90

o

elbows are used.

3)

Minimum distance between elbows is 2 ft. (0.6m).