Table L: Category I Vertical Venting

* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
When vertical height exceeds 25 ft, consult factory prior to installation.
** Subtract 10 ft per elbow. Max. 3 elbows.
Maximum combustion air duct length terminated at 100 equivalent ft.

load. Consult available guides for proper sizing of the
manifold and the chimney. At no time should the area
of the common vent be less than the area of the
largest heater exhaust outlet.

Common venting systems may be too large once an
existing unit is removed. At the time of removal of an
existing appliance, the following steps must be fol-
lowed
with each appliance remaining connected to the
common venting system placed in operation, while the
other appliances remaining connected to the common
venting system are not in operation.

WARNING: Vent connectors serving appliances
vented by natural draft shall not be connected into
any portion of mechanical draft systems operating
under a positive pressure.

CAUTION: Vent connectors for natural draft
venting systems must be Type B or better.

1.

Seal any unused opening in the common venting
system.

2.

Visually inspect the venting system for proper size
and horizontal pitch and verify there is no block-
age, restriction, leakage, corrosion or other unsafe
condition.

3.

Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the com-
mon venting system are located and other spaces
of the building. Turn on clothes dryers and any ap-
pliance not connected to the common vent
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, at maximum

Model

No.

Certified

Venting

Material

Vent

Size

Vertical Venting

Height*

Combustion

Air

Intake Pipe

Material

Air Inlet Max. Length**

Min.

Max.

6”

8”

10”

12”

399B

Category I

(Type B

Equivalent)

6”

5’

25’

Galvanized

Steel,

PVC, ABS,

CPVC

100’

499B

75’

100’

649B

8”

40’

749B

899B

989B

10”

75’

100’

1259B

12”

1529B

1799B

14”

40’

75’

1999B

2069B

2339B

16”