Hydronic heating – Raypak 399B-2339B User Manual

Page 16

background image

Cold Water Run

Cold water run differs from cold water start in that the
system water entering the heater remains below 105ºF
(41ºC) continuously. Typically, this is the case in swim-
ming pool heating and water source heat pump
applications as well as some others. If the system
water is kept in a narrow temperature range, a perma-
nent manual bypass can be employed and manually
adjusted to achieve an inlet temperature of 105ºF
(41ºC) or higher. An injector pump arrangement may
also be utilized to keep the heater loop at or above
105ºF (41ºC). An injector pump approach has the
added value of being able to adjust to changes in the
system water coming back to the heater take-off.

Table G: Heater Rates of Flow and Pressure Drops

Notes:

1. Basis for minimum flow: Models 399–899, 20 gpm or 40°F ΔT. Models 989–2339, 30 gpm or 40°F ΔT.
Basis for maximum flow: Models 399–899, 90 gpm. Models 989–2339, 132 gpm.

2. Flow switch will not operate if flow is less than 20 gpm.

as the system heats up, the outlet temperature may
continue to climb and actuate the high limit, thereby
shutting down the heater. Thus an automatic valve
system, such as a three-way proportional valve or a
modulating two-way valve to control the bypass,
should be utilized.

Temperature & Pressure Gauge

The temperature and pressure gauge is factory-
mounted in the in/out header.

Hydronic Heating

Pump Selection

In order to ensure proper performance of your heater
system, you must install a correctly sized pump. Ray-
pak recommends using a 20°F ΔT as design ΔT. (ΔT is
the temperature difference between the inlet and out-
let water when the heater is firing at full rate). If a ΔT
of larger than 20°F is necessary, see Table G and
Table H for flow rate requirements.

Model

No.

10°F ΔT

20°F ΔT

30°F ΔT

Min. Flow

Max. Flow

gpm

ΔP (ft)

gpm

ΔP (ft)

gpm

ΔP (ft)

gpm

ΔP (ft)

ΔT

gpm

ΔP (ft)

ΔT

399B

67

5.5

34

1.4

22

0.6

20

0.5

34

90

10.0

7

499B

84

9.1

42

2.3

28

1.1

21

0.6

40

90

10.4

9

649B

55

4.1

36

1.8

27

1.1

40

90

10.8

12

749B

63

5.7

42

2.6

32

1.5

40

90

11.3

14

899B

76

8.3

50

3.8

38

2.2

40

90

11.7

17

989B

83

5.2

55

2.3

42

1.3

40

132

13.1

13

1259B

106

9.6

71

4.3

53

2.4

40

132

14.8

16

1529B

129

15.7

86

7.1

64

4.0

40

132

16.5

19

1799B

101

10.7

76

6.0

40

132

18.3

23

1999B

112

13.8

84

7.9

40

132

19.0

25

2069B

116

14.8

87

8.5

40

132

19.0

26

2339B

132

21.4

98

12.1

40

132

21.4

30

16