HUMIDIFIER MANDATORY PRE-START UP CHECKLIST
Unit Serial #: _________________No. of humidifiers: _______ Tag: _______________
Unit type: _______
__________Voltage: _____V/___ph
Steam output: ____lbs/hr
Customer/Job: ______________ Address: _____________________________
Inspected by: ________________Date of inspection: ____/____/____
WATER QUALITY:
Well water
___
City water
___
Softened water
___
RO / DI water
___
Conductivity: _______ mhmos
Hardness: _____ gr.
HUMIDIFIER MOUNTING:
Clearances around the unit
Acceptable
Obstruction
– Front (door opens freely?)
3 ft min. ______________________
– Top (steam lines)
2 ft min. ______________________
– Bottom (fill, drain, controls)
2 ft min. ______________________
– Right (main pwr)
2 ft min. ______________________
STEAM LINES:
– Slope up 2 in. per 12 in.
___
– Slope down 0.500 in. per 12 in.
___
– Traps
___
– Insulated
___
– Length/Size _____/_______
CONDENSATE LINES:
– Sloped back to drain
___
– Trapped 2 in. more than static
duct pressure
___
– Size _______
– Stainless steel
___
or plastic
___
– ____% Vertical ____% Horizontal
– 90 degree elbows
___
qty: ____ – 45 degree Elbows
___
qty: ____
– Can condensate be trapped anywhere in the steam line? yes
___
no
___
WATER LINES:
– 0.050 in. at max 4ft from the unit
___
– 3/8 in. connection at fill
G
– Water pressure: 30-80 psig
___
–
PVC
___
– Stainless steel
___
DRAIN LINES:
– Air gap located within 3 ft of the unit
___
– Sloped to drain
___
–
Size:________
CYLINDER:
– Cylinder properly installed and sitting upright
WIRING:
– No loose wires around the unit or on the PC board? yes
___
no
___
CONTROLS:
Installed Location / Wiring /Setting Installed Location / Wiring /Setting
– High limit:
___
____________________ – Air proving:
___
____________________
– Mod controller:
___
________________– Other:
___
________________________
POWER:
– Voltage, amperage rating and fuse correspond to Spec Label:
___
– Disconnect switch located close to humidifier:
___