10-20

Page 42

2008-08-28

Table 4. Status Messages with LED State

NHTC Display Message

LED state

System Action

Idle

None

Unit is made idle.

Humidifying

GRN (after steam
production starts)

The unit has closed the contactor and is sending
current to the cylinder to humidify.

MANUAL DRAIN: ON

YEL (blink)

The drain valve is activated.

SAFETY LOOP; OPEN

GRN
(blink)

Steam production stopped.

LEVEL SENSOR; ON

None

Deactivates the fill valve to prevent overfilling.

KEEP WARM ACTIVATED

None

Keep Warm feature activated, it has closed the
contactor to warm the water.

W19: Cylinder spent

YEL, GRN

The electronics allow the cylinder to be reset up
to four times before locking out the humidifier.

E19: Cylinder spent

YEL, RED

Humidifier interrupts operation and the fault relay
is activated.

FOAM: FULL TANK FLUSHING

None

The unit will initiate a flush of the cylinder and
resume operation.