Nortec NH Series User Manual
Page 21
10-10
Page 14
2008-08-28
Table 1. Maximum Recommended Length of Steam Line
Unit Size
Steam Output
Distance
Possible Loss
Steam Line Size
NH-005
5 lbs/hr
8 feet 1.0
lbs/hr
3/4
NH-010
10 lbs/hr
15 feet 1.5
lbs/hr
3/4
NH-020
20 lbs/hr
20 feet *
2.0 lbs/hr
3/4
NH-030
30 lbs/hr
25 feet *
2.5 lbs/hr
3/4
NH-050
50 lbs/hr
40 feet **
4.0 lbs/hr
1 ½”
NH-075
75 lbs/hr
50 feet **
5.0 to 10.0 lbs/hr
1 ½”
NH-100
100 lbs/hr
50 feet **
5.0 to 10.0 lbs/hr
1 ½”
NH-150
150 lbs/hr
50ft/cylinder **
5.0 to 10.0 lbs/hr
1 ½” cyl
NH-200
200 lbs/hr
50ft/cylinder **
5.0 to 10.0 lbs/hr
1 ½” cyl
* Use one inch copper steam line for longer runs.
** Use two inch copper steam line for longer runs.
Notes:
1. This table gives the maximum recommended steam run by unit size.
2. The use of steam line other then copper, stainless steel tube or Nortec supplied steam line will void the
warranty and may adversely effect the operation of the humidifier
3. The NH-150 and NH-200 are dual units.
Table 2. Steam Line Materials
NORTEC Steam Line
Copper Tube (Potable)
Stainless Steel Tube
(RO or DI)
Short Run < 10 feet (3m)
yes
yes
yes
Long Run > 10 feet (3m)
no
yes
yes
NOTE
Do not use plastic, steel, or black iron. Long runs affect accuracy of humidifier and its ability to quickly
respond to changes in demand when tight control is required.
Table 3. Recommended Materials and Sizes for Steam Runs
Unit Size
Steam Run
Steam Line Material
Steam Line Description
lbs/hr kg/hr ft m
0-30
0-13 0-10
0-3
Copper Tube
0.750 in MED-L Tubing (0.875 inch OD)
0-30
0-13
30+
3+
Copper Tube
1.0 inch MED-L Tubing (1.125 inch OD)
0-30 0-13
0-10
0-3 Stainless
Steel
Tube
0.875 inch Tube x 0.049 inch thick
0-30
0-13
30+
3+
Stainless Steel Tube
1.125 inch Tube x 0.049 inch thick
50-100
22-45 0-20
0-6
Copper Tube
1.500 in MED-L Tubing (1.625 inch OD)
50-100
22-45 20+
6+
Copper Tube
2.0 inch MED-L Tubing (2.125 inch OD)
50-100
22-45 0-20
0-6
Stainless Steel Tube
1.750 inch Tube x 0.065 inch thick
50-100
22-45 20+
6+
Stainless Steel Tube
2 inch Tube x 0.065 inch thick
NOTE
Options show in bold-italic font require that reducers be used at both ends. These extra large sizes are
to allow for better condensation removal in long steam runs. These sizes do not permit the use of hose
couplings to connect either humidifier or distributors.
Insulate steam lines with 1” pipe insulation.