2. CHECK LISTS

A.

PRE-NORTEC ONLINE START UP CHECKLIST WIRING
(1) Humidifier-to-Humidifier

Connection:

Each individual Humidifier linked
to lead Unit.

Connection can be direct or
daisy-chained to other units.

(2) Network Connection:

Lead Unit wired to Local Network
(Ethernet, GPRS, Dial-up).

Network activity verified.

(3) Controls Wired:

Directly to humidifiers.

(4) Start-Up Procedure:

Ensure power is being supplied

to the humidifier and Nortec
Online Module.

Verify power to NetBiter (Power
LED should be lit).

After power-up, verify network
communication.

Verify variable operation after
mapping is complete.

Perform regular humidifier
start-up check.

B.

PRE-NORTEC LINKS START-UP CHECKLIST
(1) Humidifier-to-Humidifier

Connection:

Each individual Humidifier linked
to lead Unit.

Connection can be direct or
daisy-chained to other units.

(2) Network Connection:

Lead Unit wired to Local BMS.

Network activity verified.

(3) Controls Wired:

Directly to humidifiers.

(4) Start-Up Procedure:

Verify power to NORTEC Links

module.

Verify power to I/O-Controller.

Adjust Network address dials to

desired address (BACnet/IP
address is preset at factory).

After power-up, verify network

communication.

Map desired network variables to

BMS.

Verify variable operation after

mapping is complete.

Perform regular humidifier start-

up check.