Chapter 3

Signal Connections

SCXI-1161 User Manual

3-2

© National Instruments Corporation

Figure 3-1. Contact Protection Using a Flyback Diode for DC Inductive Loads

In addition, the module has pads on which you can place an arc
suppressor protection circuit to limit the voltage spike generated during
the switching of inductive loads. These pads are between the COM
position and the NO position and between the COM position and the NC
position of the relays.

To determine where to place each arc suppressor, refer to Tables 3-1
and 3-2, which indicate the channel and suppressor pad assignments.

Table 3-1. Arc Suppressor Placement, COM to NO

COM to NO

Channel Number

Transient Voltage Suppressor

Reference Designator

0

VR1

1

VR3

2

VR5

3

VR7

4

VR9

5

VR11

6

VR13

7

VR15

V

NC

COM

NO

VDC

Inductive Load

Flyback Diode

+

-