Table 3. Furnace Dimensions and Shipping Weights

Table 4. Minimum Clearances to Combustible Materials

CLEARANCES TO COMBUSTIBLE MATERIALS

This furnace is Designed Certifi ed by CSA International for the minimum clearances to combus-
tible material listed in Table 4. See the furnace name plate, located inside the furnace cabinet, for
specifi c model number and clearance information.

services both the appliance and the
carbon monoxide detector;

b. Have battery back-up power;
c.

Meet ANSI/UL 2034 Standards
and comply with NFPA 720 (2005
Edition);and

d. Have been approved and listed by

a Nationally Recognized Testing
Laboratory as recognized under 527
CMR.

3. A Product-approved vent terminal must

be used, and if applicable, a Product-
approved air intake must be used. In-

stallation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.

4. A metal or plastic identifi cation plate

shall be mounted at the exterior of the
building, four feet directly above the lo-
cation of vent terminal. The plate shall
be of suffi cient size to be easily read
from a distance of eight feet away, and
read “Gas Vent Directly Below”.

Model

Number

Furnace

Btuh

Dimensions (inches)

Shipping

Weight

(lbs)

A

B

C

D

*RC040

40,000

14 1/4

12 3/4

5 1/8

11 3/4

133

*RC060

60,000

14 1/4

12 3/4

5 1/8

11 3/4

140

*RC080

80,000

19 3/4

18 1/4

7 7/8

17 1/4

172

*RC100

100,000

19 3/4

18 1/4

7 7/8

17 1/4

180

*RC120

120,000

22 1/2

21

9 1/4

20

204

*RL040

40,000

14 1/4

12 3/4

4 5/8

12 3/4

135

*RL060

60,000

14 1/4

12 3/4

4 5/8

12 3/4

135

*RL080

80,000

19 3/4

18 1/4

10

18 1/4

174

*RL100

100,000

19 3/4

18 1/4

10

18 1/4

185

*RL120

120,000

22 1/2

21

12 1/2

21 1/8

209

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIAL

Furnace

Cabinet

Minimum Clearances (Inches)

Input

Width

(Btuh)

(Inches)

Side

Vent

Back

Top

Front

40,000

14 1/4

0

0

0

1

1*

60,000

14 1/4

0

0

0

1

1*

80,000

14 1/4

0

0

0

1

1*

100,000

19 3/4

0

0

0

1

1*

120,000

22 1/2

0

0

0

1

1*

* When installed horizontally, 24 inches is required for servicing.