VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

1

In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code

2

In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves

both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
* For clearances not specifi ed in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the manufacturer’s

installation instructions.”

Figure 19. Vent Termination Clearances for Direct Vent Furnaces

Canadian Installations

1

US Installations

2

A = Clearance above grade, veranda, porch,

deck, or balcony

12 inches (30 cm)

12 inches (30 cm)

B = Clearance to window or door that may be

opened

6 inches (15 cm) for appliances 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,00 Btuh (30 kW), 36 inches (91 cm)
for appliances >100,00 Btuh (30 kW)

6 inches (15 cm) for appliances 10,000
Btuh (3 kW), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000 Btuh (15 kW), 12 inches (30 cm)
for appliances > 50,000 Btuh (15 kW)

C = Clearance to permanently closed window

*

*

D = Vertical clearance to ventilated soffi t

located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal

*

*

E = Clearance to unventilated soffi t

*

*

F = Clearance to outside corner

*

*

G = Clearance to inside corner

*

*

H = Clearance to each side of center line

extended above meter/regulator assembly

3 feet (91 cm) within a height 15 feet
above the meter/regulator assembly

*

I = Clearance to service regulator vent outlet

3 feet (1.83 m)

*

J = Clearance to nonmechanical air supply inlet

to building or the combustion air inlet to any
other appliance

6 inches (15 cm) for appliances 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,00 Btuh (30 kW), 36 inches (91 cm)
for appliances >100,00 Btuh (30 kW)

6 inches (15 cm) for appliances 10,000
Btuh (3 kW), 9 inches (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000 Btuh (15 kW), 12 inches (30 cm)
for appliances > 50,000 Btuh (15 kW)

K = Clearance to a mechanical air supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet
(3 m) horizontally

L = Clearance above paved sidewalk or paved

driveway located on public property

7 feet (2.13 m) †

*

M = Clearance under veranda, porch deck, or

balcony

12 inches (30 cm) ‡

*