Verifying burner operation, Verifying operation of the supply air limit switch, Description of components – Nordyne RL 90+ User Manual
Page 34

34
Table 13. Gas Flow Rate
control board. Reconnect the desired blower tap
to the piggyback quick connect.
The blower control is designed to start the
circulating air blower 30 seconds after the gas
valve is opened. The blower control is factory
wired to turn the blower motor off 120 seconds
after the gas valve is closed. This timing can be
changed using the BLOWER OFF timing switch
opposite the terminal block on the control board.
(See Figure 28.)
Verifying Burner Operation
To verify operation of the burners, make sure
that the blower compartment door is in place
and that there is power to the furnace. Set the
thermostat above room temperature and ob-
serve the ignition sequence. The fl ame can be
observed through the small clear window on the
burner box. The burner fl ame should carry over
between all burners. The fl ames should be blue,
without yellow tips. Flames should extend from
each burner without lifting, curling, or fl oating.
After verifying ignition, set the thermostat below
room temperature and verify that the burner fl ame
extinguishes completely.
Verifying Operation of the Supply
Air Limit Switch
To verify operation of the supply air limit switch,
make sure that the blower door is in place and
that there is power to the furnace. Completely
block the return airfl ow to the furnace by installing
a close-off plate in place of or upstream of the
fi lter(s). Set the thermostat above room tempera-
ture and verify that the Sequence of Operation
is as described in these instructions. The supply
air limit switch should function to turn off the
gas valve within approximately fi ve minutes. The
circulating air and combustion blowers should
continue to run when the supply air limit switch
opens. Remove the close-off plate immediately
after the supply air limit switch opens. If the
furnace operates for more than fi ve minutes
with no return air, set the thermostat below room
temperature, shut off the power to the furnace,
and replace the supply air limit switch.
DESCRIPTION OF COMPONENTS
Figure 28 shows the location of each of the
functional components described below. If any
component of the furnace must be replaced,
use only factory authorized replacement parts.
See the Replacement Parts List for each com-
ponent.
Flame Sensor – The fl ame sensor acts to prove
that fl ame has carried over from the igniter to the
opposite end burner. If no fl ame is sensed, the
furnace will be shut down automatically.
Gas Valve – The gas valve controls the fl ow
of gas to the burners. When the gas valve is
energized it automatically opens and regulates
the gas pressure in the manifold.
Pressure Switch – The pressure switch verifi es
that the inducer is drawing the combustion gases
GAS FLOW RATE (CUBIC FEET PER HOUR)
TIME FOR
ONE REVOLUTION
(SECONDS)
CUBIC FEET PER REVOLUTION OF
METER
TIME FOR
ONE REVOLUTION
(SECONDS)
CUBIC FEET PER REVOLUTION OF
METER
1
5
10
1
5
10
24
150
750
1500
80
45
225
450
26
138
692
1385
82
44
220
439
28
129
643
1286
84
43
214
429
30
120
600
1200
86
42
209
419
32
113
563
1125
88
41
205
409
34
106
529
1059
90
40
200
400
36
100
500
1000
92
39
196
391
38
95
474
947
94
38
191
383
40
90
450
900
96
38
188
375
42
86
429
857
98
37
184
367
44
82
409
818
100
36
180
360
46
78
391
783
102
35
176
353
48
75
375
750
104
35
173
346
50
72
360
720
106
34
170
340
52
69
346
692
108
33
167
333
54
67
333
667
110
33
164
327
56
64
321
643
112
32
161
321
58
62
310
621
114
32
158
316
60
60
300
600
116
31
155
310
62
58
290
581
118
31
153
305
64
56
281
563
120
30
150
300