Upfl ow furnaces downfl ow furnaces, 19 figure 16. horizontal venting, Table 5. vent table – Nordyne RL 90+ User Manual

Page 19

background image

19

Figure 16. Horizontal Venting

* These neoprene couplings are fi eld-supplied and can be used if the installation requires breakable connections in the piping.

Note that a maximum of two couplings per pipe are allowed.

Upfl ow Furnaces

Downfl ow Furnaces

**NOTES

1.

Subtract 2.5 ft. for each additional 2” long radius elbow, 5 ft. for each additional 2” short radius elbow, 3.5’
for each additional 3” long radius elbow, and 7’ for each additional 3” short radius elbow.

2.

Two 45 degree elbows are equivalent to one 90 degree elbow.

3.

Do not include termination elbows in calculation of vent length

4.

This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease vent pipe
lengths by 8% per 1000 ft. of altitude.

5.

Only the above pipe materials are approved for use with these condensing furnaces.

Table 5. Vent Table

5/8"

Inlet

Exhaust

Combustion

Offset with
Exhaust Pipe
for Adequate
Dimensional
Clearance

PVC or
ABS Pipe

See Vent Table 5

Straps or Other Suitable

Supports at Minimum of 5 ft. Intervals

Upward Pitch - 1/4" per Foot

Outlet Exhaust Vent

First Support Placed
as Close to Furnace
Connection as Possible

Exhaust Vent

Wall

Seal/Caulk
around Pipe
at Building

90˚ Elbow

12" Min.

Normal Snow Level

7"

Straight Neoprene Coupling
with 2 Hose Clamps*
(Optional - Not Shown)

5/8"

Inlet

Exhaust

Combustion Air

Inlet

Offset with Exhaust
Pipe for Adequate
Dimensional
Clearance

PVC or
ABS Pipe

See Vent Table 5

Straps or Other Suitable

Supports at Minimum of 5 ft. Intervals

Upward Pitch - 1/4" per Foot

Outlet Exhaust Vent

First Support Placed

as Close to Furnace

Connection as Possible

Exhaust Vent

Wall

Seal/Caulk
around Pipe
at Building

90˚ Elbow

12" Min.

Normal Snow Level

Straight Neoprene
Coupling with
2 Hose Clamps*

APPLICATION

SINGLE PIPE LENGTH (ft.)

with 1 long radius elbow*

DIRECT VENT, DUAL PIPE LENGTH (ft.)

with 1 long radius elbow on each pipe*

PVC,CPVC or ABS

Outlet

Outlet

Inlet/Outlet

Inlet/Outlet

Inlet/Outlet

SCH. 40 Pipe Size

2”

3”

2”

2”

3”

2”

3”

3”

Models 040

80

150

40

40

50

50

90

90

Models 060 & 080

60

150

30

30

35

35

90

90

Models 100 & 120

30

150

15

15

25

25

90

90