beautypg.com

5 functional description, 5 functional description -31, Smart i/o user’s manual – Pepper Computer Modular Computers RS485 User Manual

Page 187: Chapter 5 analog modules

background image

SMART I/O User’s Manual

©1996 PEP Modular Computers GmbH

March 12, 1996

Page 5 - 31

5

Chapter 5 Analog Modules

5.2.5 Functional Description

Figure 5.2.5.1: SM-PT100 Schematic Diagram

The SM-PT100 has provision for 4 sets of 4-wire PT100 sensors driven by

an on-board generated 400

µ

A constant current source. The differential

analog input consists of a channel multiplexer, operational amplifier voltage

feedback impedance converter and a high-resolution 16-bit delta-sigma

converter. 1000V DC system isolation is provided by an optoisolated DC/DC

converter while system flexibility is provided by a 256 bytes of serial

EEPROM for ID number, production and board-specific calibration data.

Two front-panel LEDs show the conversion/calibration activity.

The PT100 is a platinum resistance, which at 0ºC has a resistance of 100

and conforms to the international DIN IEC 751 standard for Industrial

Platinum Resistance Thermometer Sensors. Two classes A and B exist under

this standard with class B experiencing a slightly worse initial error.

Figure 5.2.5.2 Supported Sensor Connections

Multiple

xe

r

A/D

Con

ve

rter

System

Interface

LED

Driver

Impedance

Con

ve

rter

Serial

I/O

R

L

R

L

PT100 Sensor , 4-wire Input

CUR

IN+

IN-

AGND

400

µ

A

400

µ

A

SENSE LINE

SUPPLY LINE

SUPPLY LINE

SENSE LINE

User Interface

System Interface

Pt 100/ /2

Red

White

Pt 100/ /3

Red

White

Red

Pt 100/ /4

Red

White

Red

Red