Outdoor fan motor operation – Philips CS-E15DB4EW User Manual
Page 23
![background image](/manuals/187123/23/background.png)
D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→ 2 → 3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→ 5 → 6 → 7 → 6 ←→ 7
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
Odor Status
1
2
3
4
5
6
7
6.7.6...
1
Status Shift
according to COMP
ON
OFF
ON
Status Shift
according
Cooling
zone
40
50
—
30
90
20
90
20.90.20...
to time (s)
Dry zone
ON
Fan Speed
Cooling
zone
OFF
SSLo
Auto Fan Speed
SSLo
OFF
SSLo
OFF
SSLo.OFF...
Dry zone
SLo
8.1.7. Outdoor Fan Motor Operation
Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation for speed no.8.
No.
RPM during Fan Speed (rpm)
E21D
E18D
E15D
15
75
73
71
14
75
73
71
13
70
68
66
12
68
66
64
11
64
62
60
10
62
60
60
9
58
58
58
8
50
50
50
7
45
45
45
6
40
40
40
5
35
35
35
4
30
30
30
3
25
25
25
2
20
20
20
1
15
15
15
23
CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE