beautypg.com

Philips CS-E15DB4EW User Manual

Page 18

background image

8.1.2. Cooling Operation

8.1.2.1. Thermostat control

• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point.

8.1.3. Soft Dry Operation

8.1.3.1. Thermostat control

• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF

point.

8.1.4. Heating Operation

8.1.4.1. Thermostat control

• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF

point.

18

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE