Powerware FCC 15 User Manual
Page 25
INTEGRATING THE UPS
EATON Powerware
®
Modbus
®
Card User’s Guide
S 164201376 Rev C www.powerware.com
21
Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000)
Register
Meter Name
Scale
Unit
1
OUTPUT VOLTS AB
/10
Volts
2
OUTPUT VOLTS BC
/10
Volts
3
OUTPUT VOLTS CA
/10
Volts
4
INPUT VOLTS AB
/10
Volts
5
INPUT VOLTS BC
/10
Volts
6
INPUT VOLTS CA
/10
Volts
10
BYPASS VOLTS AB
/10
Volts
11
BYPASS VOLTS BC
/10
Volts
12
BYPASS VOLTS CA
/10
Volts
19
INPUT CURRENT PHASE A
/10
Amps
20
INPUT CURRENT PHASE B
/10
Amps
21
INPUT CURRENT PHASE C
/10
Amps
22
OUTPUT TRUE POWER
/10
kW
23
INPUT TRUE POWER
/10
kW
24
OUTPUT APPARENT POWER
/10
kVA
25
INPUT APPARENT POWER
/10
kVA
26
OUTPUT POWER FACTOR
/100
—
27
INPUT POWER FACTOR
/100
—
28
OUTPUT FREQUENCY
/10
Hz
29
INPUT FREQUENCY
/10
Hz
30
INVERTER FREQUENCY
/10
Hz
31
BYPASS FREQUENCY
/10
Hz
33
BATTERY CURRENT
/10
Amps
34
BATTERY VOLTAGE
/10
Volts
35
% BATTERY LEFT
/10
%
36
BATTERY TIME REMAINING
/10
Minutes
60
INVERTER VOLTS PHASE A
/10
Volts
61
INVERTER VOLTS PHASE B
/10
Volts