Powerware FCC 15 User Manual
Page 24

INTEGRATING THE UPS
EATON Powerware
®
Modbus
®
Card User’s Guide
S 164201376 Rev C www.powerware.com
20
Unit
Format
Value
Name
Register
162
Building Alarm 2
1
BOOL
Status
163
Building Alarm 1
0
BOOL
Status
169
Output overload
0
BOOL
Status
172
DC link over voltage
0
BOOL
Status
173
DC link under voltage
0
BOOL
Status
174
Rectifier failed
0
BOOL
Status
176
Battery contactor fail
0
BOOL
Status
177
Bypass breaker fail
0
BOOL
Status
191
Battery current limit
0
BOOL
Status
194
Output current over 100%
0
BOOL
Status
199
Shutdown imminent
0
BOOL
Status
200
Battery low
0
Status
212
Battery DC over voltage
0
BOOL
Status
214
Power supply failure
0
BOOL
Status
229
Network not responding
0
BOOL
Status
241
Emergency shutdown command
0
BOOL
Status
249
Bypass not available
0
BOOL
Status
251
Battery contactor open
0
BOOL
Status
252
Inverter contactor open
0
BOOL
Status
270
Battery totally discharged
0
BOOL
Status
295
Battery not charged
0
BOOL
Status
312
UPS On Battery
0
BOOL
Status
313
UPS On Bypass
1
BOOL
Status
314
Load Dumped (Load Power Off)
0
BOOL
Status
337
Fan Failure
0
BOOL
Status
345
Transformer Over Temperature
0
BOOL
Status
361
Input Breaker Failed
0
BOOL
Status