Chapter 5 integrating the ups, Generating modbus data, Integrating the ups – Powerware FCC 15 User Manual

Page 21

background image

EATON Powerware

®

Modbus

®

Card User’s Guide

S 164201376 Rev C www.powerware.com

17

Chapter 5

Integrating the UPS

Powerware provides a software tool named Modbus Profiler that
creates a Modbus register map specifically for your Powerware UPS.
Refer to the Master Modbus Register Map for a complete list of the
Status, Alarm, and Meter data for all Powerware UPS equipment (open
the reg_map.pdf file in the directory where the Modbus Profiler tool is
located).

You need the following system requirements to install the Modbus
Profiler tool:

S

Microsoft

®

Windows

®

9x, NT, 2000, or XP operating system

S

100 KB of free hard drive space

S

100 KB of free RAM

S

An open RS-232 communication port on your computer

S

A working Internet connection

Generating Modbus Data

To generate Modbus data that your building management software
needs to poll UPS information:

1.

Connect the supplied serial cable from the configuration port on the
Modbus Card to an available RS-232 communication port on your
computer (see Figure 14).

Configuration
Port

Figure 14. Configuration Port

2.

Create a directory on your computer for the Modbus Profiler tool,
such as: c:\ModbusProfiler

3.

Download the Modbus Profiler tool from the Powerware Web site
at: http://www.powerware.com/software/modbus_profiler.asp

4.

Unzip the files to the directory created in Step 2.