INTEGRATING THE UPS
EATON Powerware
®
Modbus
®
Card User’s Guide
S 164201376 Rev C www.powerware.com
19
Unit
Format
Value
Name
Register
113
Rectifier Input Status
1
BOOL
Status
114
Bypass Status
0
BOOL
Status
115
Bypass Input Status
1
BOOL
Status
116
Input Circuit Breaker Status (CB1)
1
BOOL
Status
117
Battery Disconnect Status
1
BOOL
Status
118
Inverter Disconnect Status
1
BOOL
Status
119
Inverter Status
1
BOOL
Status
120
UPM Normal
0
BOOL
Status
121
UPM On Battery
0
BOOL
Status
122
UPM Bypass (Off Line)
0
BOOL
Status
123
UPM Notice
0
BOOL
Status
124
UPM Alarm
0
BOOL
Status
125
UPM Standby
0
BOOL
Status
144
Inverter AC over voltage
0
BOOL
Status
145
Inverter AC under voltage
0
BOOL
Status
146
Inverter under or over frequency
0
BOOL
Status
147
Bypass AC over voltage
0
BOOL
Status
148
Bypass AC under voltage
0
BOOL
Status
149
Bypass under or over frequency
0
BOOL
Status
150
Input AC over voltage
0
BOOL
Status
151
Input AC under voltage
0
BOOL
Status
152
Input under or over frequency
0
BOOL
Status
153
Output AC over voltage
0
BOOL
Status
154
Output AC under voltage
0
BOOL
Status
155
Output under or over frequency
0
BOOL
Status
158
Building Alarm 6
0
BOOL
Status
159
Building Alarm 5
0
BOOL
Status
160
Building Alarm 4
0
BOOL
Status
161
Building Alarm 3
0
BOOL
Status