Chapter 1 introduction – Powerware 9125 User Manual
Page 5

EATON Powerware
®
9125 Two-in-One EBM (700–2000 VA) User’s Guide
S 05146489 Rev D www.powerware.com
1
Chapter 1
Introduction
The Extended Battery Module (EBM) can be added to the 700–2000 VA
Powerware
®
9125 uninterruptible power system (UPS) to extend the
available battery time (see Table 1). Up to four EBMs can be installed
with the Powerware 9125 UPS.
Table 1. Battery Runtimes (in Minutes)
700–1000 VA Models
Load
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
200 VA/140W
37
271
546
400 VA/280W
19
142
278
700 VA/490W
9
72
156
850 VA/595W*
6
59
124
1000 VA/700W*
5
48
104
* Runtimes do not apply for 700 VA models.
1250–2000 VA Models
Load
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
400 VA/280W
46
177
331
501
682
700 VA/490W
25
96
180
272
370
850 VA/595W
21
76
142
214
292
1000 VA/700W
16
61
115
174
237
1250 VA/875W
11
46
87
131
179
1500 VA/1050W**
8
37
70
106
144
1800 VA/1260W***
6
30
57
85
116
2000 VA/1400W***
5
26
49
74
100
** Runtimes do not apply for 1250 VA models.
*** Runtimes do not apply for 1250 VA and 1500 VA models.
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.