When to Replace Batteries
When the
indicator flashes, the batteries may need replacing.
Conduct a self-test by pressing and holding the
button for three
seconds. After the test is complete, the
indicator should turn off (it
may take a few seconds to turn off). If the
indicator continues to
flash, contact your service representative to order new batteries.
How to Replace Extended Battery Modules
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot-swappable battery feature, UPS batteries can be replaced
easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries, see
“Turning the UPS Off” in the UPS user’s guide.
Consider all warnings, cautions, and notes before replacing batteries.
W A R N I N G
S
Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
S
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
C A U T I O N
The EBM is heavy (29.5 kg/65 lb). A minimum of two people are required to lift the cabinet
into the rack.
To replace the EBMs:
1.
Unplug the EBM cable from the UPS.
If additional EBMs are installed, unplug the EBM cable from the
battery connector on each EBM.
2.
If the EBM is in a tower configuration, remove the joining brackets.
3.
If the EBM is in a rack, install the supplied mounting handles and
brackets on the new EBM.