beautypg.com

PVI Industries PV500-45U User Manual

Page 18

background image

18

PV500-45U 06/12

 

8.2 Maximum Allowed Remote Combustion Air Inlet Length (Equivalent Length)

A vertical or horizontal remote air inlet system can be connected to this appliance without modification. The

maximum length of field supplied single wall pipe, such as galvanized ventilation pipe, is shown in the chart below
titled Maximum Air Inlet Duct Equivalent Length. Use metal tape or RTV sealant to seal each pipe joint.

Maximum Air Inlet Duct Equivalent Length

Duct Size

6” Duct

7” Duct

8” Duct

9” Duct

Max Equivalent Length

100 feet

130 feet

250 feet

450 feet


To determine the maximum straight length of duct allowed, use the Duct Fitting Equivalent Length chart below to find
the total equivalent length for all duct fittings in your combustion air system. Then subtract this number of feet from
the total equivalent length allowed in Maximum Air Inlet Duct Equivalent Length chart above. The sum of this
calculation is the maximum length of straight duct allowed. If a longer length is required, repeat the calculation using
a larger duct size. No additional deduction is required for the addition of the duct system terminal.

Duct Fitting Equivalent Length

Duct Pipe:

6” Duct

7” Duct

8” Duct

9” Duct

90º Elbow

8 feet

9 feet

10 feet

11 feet

90º Long Radius Elbow

5 feet

5 feet

5 feet

6 feet

45º Elbow

5 feet

5 feet

5 feet

5 feet


The following remote air duct information is provided for use in design calculations, if needed.

Remote Air Duct Specifications

Input MBtu

Required Air (SCFM)

399 87

500 108

750 163

900 195

1000 217


8.3 Remote Combustion Air Cap

A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent termination to

adequately protect the combustion air inlet from wind and weather. A UL Listed air intake termination cap is available
from PVI Industries and may have shipped with the water heater as a purchased option.

8.4 Vertical or Horizontal Remote Air Duct Termination

 Air inlet and exhaust vents should terminate in the same wind pressure area whenever possible.

 Air inlet must be located no less than 3 feet (0.91m) below the exhaust terminal if they are within 10 feet (3.05 m)

of each other.

 If terminating through the roof, the air inlet must terminate at least 12 inches (0.3 m) above roof level and at least

12 inches (0.3 m) above snow levels.

 If terminating through a sidewall, the air inlet must terminate at least 12 inches (0.3 m) above grade and/or at

least 12 inches (0.3 m) above normal snow levels.