beautypg.com

PVI Industries 1500 N 600A-TPL User Manual

Low no, Turbopower, Packaged water heater nickelshield

background image

LOW NO

x

TURBOPOWER

®

• PACKAGED WATER HEATER

NICKELSHIELD

®

NICKEL-PLATED STORAGE TANK

TANK SERIES 600 GALLONS VERTICAL


Recovery gph

c

Dimensions

(inches)

Blower

Motor

MODEL

NUMBER

40° - 120°F 40° - 140°F

INPUT

Btu/h

Min. Inlet

Flow Gas

Pressure

" W.C.

d

SCAQMD Energy

Model No.

A B C HP Amps

Shipping

Weight

#

1000 N 600A-TPL

1000

800

800,000

4.5.

8TPL

800 MBtu/h

33

8

1

1/2

7

2430

1500 N 600A-TPL

1500

1200

1,200,000

4.5

12TPL

1200 MBtu/h

41

8

1-1/4

1

14

2710

c Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d With standard gas train
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV 6452.







Product is patented in the U.S., Canada, and Mexico.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 6529 02/25/04

(800) 784-8326

• www.pvi.com

STANDARD GAS PRESSURE REQUIREMENTS:

SEE TABLE FOR MINIMUM PRESSURE BY MODEL.

MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

CONTACT YOUR PVI REPRESENTATIVE.

VENTING REQUIREMENTS:

-.02" TO -.06" W.C. (NEGATIVE PRESSURE).

TYPE B VENTING.

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON

THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK

NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."

STANDARD ELECTRICAL REQUIREMENTS:

VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.

OTHER VOLTAGES REQUIRE AN EXTERNAL

STEPDOWN TRANSFORMER.

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND

SPECIFICATION WITHOUT NOTICE.

This manual is related to the following products: