PANDUIT DPoE Power System User’s Guide

Issue 1.0

Part Number: PN380

Table 1: DPoE Power Components Available from PANDUIT Corporation

PANDUIT Part Number

Description

Individual power supply

DPoEPWRB120

Individual power supply - 120 watt power
supply – 48 volt output

DPoEPWRCM Managed

power

chassis - supports 3 rectifiers

- equipped with Network Interface Card

DPoEPWRCU Unmanaged

power chassis - supports 3

rectifiers - does not include Network Interface
Card.

DPoEPWRR500

500 watt rectifier for use in either
DPoEPWRCM or DPoEPWRCU chassis

DPoEPWRR1250

1250 watt rectifier for use in either
DPoEPWRCM or DPoEPWRCU chassis

DPoEPWRF10

10 amp fuse (package of 10)

DPoEPWRNIC

Network Interface Card

CORD-A

Power cord for Australia

CORD-E

Power cord for Europe

CORD-S

Power cord for USA

DPoE Power System

CORD-U

Power cord for the U.K.

INSTALLATION

General Practices


Observe all local and national electrical, environmental, and workplace codes.

Each chassis should be fed from a dedicated AC branch circuit of a TN or IT power system.

CAUTION:

The plug ends on the power cords used for the AC connections are
considered to be the primary disconnect means. Reasonable access must
be given to the plug and receptacle area. The receptacle must be fed with
a breaker or fuse according to Table 4: Recommended AC Circuit Breaker
and Wire Sizes
.


Use single hole, Underwriters Laboratory (U.L.) listed lugs for the bulk DC connection to prevent lug
rotation and inadvertent contact with other circuits. Terminal strip connections use compression screws.

Class 1 wire is recommended for all DC connections.

Minimum wire sizes for protected and unprotected circuits are shown in Table 5: Minimum Recommended
DC AWG for 90° C Cabling for Unprotected Outputs
, respe
ctively. In practice, loop voltage drop
considerations will usually dictate larger than minimum safe wire size.

For connection and mounting torque requirements see Table 6: Recommended Torque Settings.

PANDUIT Corp. does not recommend shipping the chassis with the rectifiers installed. Rectifiers should
be shipped in their separate boxes.