beautypg.com

Torque settings, Required tools, Site and equipment preparation – Panduit PN380 User Manual

Page 12: Table 6: recommended torque settings

background image

PANDUIT DPoE Power System User’s Guide

Issue 1.0

Part Number: PN380

Table 5: Minimum Recommended DC AWG for 90° C Cabling for

Unprotected Outputs

Total Rectifier Current
Rating (A)

Wire and Lug Gauge
(AWG) using 90

°

C wire


(NEC Table 310.16)

1

10 16
20 14
25 12
30 12
40 10
50 8
75 6

Torque Settings

The following table shows recommended torque settings for all mechanical and electrical connections
according to screw or nut size in inch pounds (in-lbs).

Table 6: Recommended Torque Settings

Screw or Nut Size

Toque (in-lbs)

4-40 6
6-32 12
8-32 22

10-32 37
12-24 50

¼-20 65

Required Tools


The DPoE Power System is designed to be installed with a minimum number of commonly available
tools:

• #1 & #2 flat blade and Phillips head screwdrivers

• Torque wrench

• 7/16” socket, ¼” drive

• Wire and cable strippers (PANDUIT part number CT-100)

• Wire and cable crimpers (such as PANDUIT part CT-1550, CT-1551, CT-1570, CT-1700

Contour Crimp

TM

Controlled Cycle Crimp Tools) (used for optional bulk DC connection)

Site and Equipment Preparation


Prior to unpacking the DPoE Power System, note any physical package damage that could indicate
potential damage to the contents. After removing DPoE Power System from the boxes and packing
material, inspect for shipping and/or other damage. Any problems should be reported to PANDUIT
technical support.

7

1

Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information

Technology Equipment,” December 2000 for non-building wiring.