beautypg.com

0 changing components – Baxi Potterton BBU 15 HE User Manual

Page 31

background image

31

© Baxi Heating UK Ltd 2009

10.0 Changing Components

10.8

Gas Valve (Fig. 51)

IMPORTANT: After replacing the valve the CO

2

must be

checked and adjusted as detailed in Section 11.0 Setting

the Gas Valve. Only change the valve if a suitable

calibrated combustion analyser is available, operated by a

competent person - see Section 9.1

1. Disconnect the plug and earth wire from the gas valve and
remove the sensing pipe from between the valve and fan
outlet.

2. Remove the gas feed pipe and washers, and extract the
injector from the gas/air inlet manifold.

3. Undo the nut on the pipe from the gas cock to the valve
inlet adaptor, and remove the screws securing the adaptor to
the boiler side panel.

4. Remove the valve complete with the inlet and outlet
adaptors, and the seal on the inner face of the side panel.
Transfer the adaptors to the new valve, using new ‘O’ rings if
necessary.

5. Replace in reverse order of dismantling, using the screws
previously removed. Examine all sealing gaskets and washers
and replace if necessary.

NOTE: To assist the boiler to light prior to final setting,

use a suitable hexagon key to wind out the Gas/Air

adjustment screw until it is flush with the valve body, then

turn the screw 4 full turns clockwise (Fig. 51). If the boiler

will not light, or the correct CO

2

cannot be achieved

contact the ‘heateam’ technical helpline.

PCB Control Box
removed for clarity

Gas Valve

Earth Wire

Injector

Fig. 51