beautypg.com

Baxi Potterton Solar User Manual

Page 6

background image

Potterton Solar - Solar Thermal Domestic Hot Water System

6

2.0

Commissioning of hydraulic station

2.4

Checking and adjusting the flow rate

Adjust the flow rate when the system is cold (20°C)

(see Fig. 5).

The flow rate should be adjusted to give the optimum

flow rate depending on the number and type of

collector panels connected.

Turn the slot of the adjusting screw (Fig. 5 Item 1) below

the return temperature gauge horizontally to close the

non-return valve.

Turn the l.h. isolating valve with integral thermometer in

the flow (Fig. 5 Item 2) as far as it will go in the direction

indicated by the arrow to close the non-return valve (dot

on bezel on top).

Turn the slot of the adjusting screw (Fig. 5 Item 3) in the

return vertically to open the flow limiter on the flow

meter (Fig. 5 Item 4).

Manually operate the solar pump (see section 3.1.7).

Set the solar pump switch (Fig. 5 Item 5) so that the

required flow rate is achieved or exceeded with the

lowest possible setting.The flow limiter adjusting screw

(Fig. 5 Item 3) can be used to fine-tune the flow rate.

Depending on the number and type of collectors installed,

set the required flow rate from table (See Table 1).

The float in the flow meter will indicate the circulation

flow rate through the flow meter sight glass.

Adjust screw of the flow limiter (Fig. 5 Item 3) with a

screwdriver, until the upper edge of the float in the sight

glass indicates the required flow rate.

Set manual pump operation to off.

2.5

Installation of the thermal insulation

Refit the controller mounting moulding (Fig. 6 Item 1)

onto the rear moulding.

Push the front thermal insulation (Fig. 6 Item 2) against

the rear thermal insulation section (Fig. 6 Item 3) until it

clips into place.

Flow rate

(when system is cold)

Collectors

l/min

1

approx. 2

2

approx. 4

3

approx. 6

Fig. 5

Fig. 6

2

5

3

4

1

2

3

1

Table 1